The AC & DC Voltage and Current Monitor (E-ACDCLM) measures and reports AC and DC voltage, and reports AC and DC current measured by external Hall effect sensors (sold separately) to E-2D/5D/16D devices.
Reports AC voltage, AC current, DC voltage, and DC current.
Current measurements require Hall effect sensors (sold separately).
Polling rate: 1 sample/second.
Common applications: power systems, power equipment, battery monitoring, generators, remote sites, Controlled Environment Vaults (CEV), building automation, data centers, server cabinets, telecom, substations, storage power systems, telecom huts, indoor/outdoor lighting, power distribution, and medical/testing equipment.
AC Voltage Input
2-pin terminal block
0 to 240VAC input, 600V isolation
Resolution: 0.25VAC
Accuracy:
0 to 220VAC: ±2.5VAC
220 to 240VAC: ±5.0VAC (at 77°F / 25°C)
DC Voltage Input
2-pin terminal block
Range: -60 to +60VDC, non-isolated
Resolution: 0.12VDC
Accuracy: ±1.2VDC
Hall Effect Sensor Interfaces
1 Rectified Hall Effect Interface (4-pin) for AC current
Resolution: 0.2%
Accuracy and range depend on sensor (sold separately)
1 Non-Rectified Hall Effect Interface (4-pin) for DC current
Resolution: 0.2%
Accuracy and range depend on sensor (sold separately)
Additional Specs
Supports CAT5/5e/6 cables up to 1,000 ft (305 m)
Dimensions (WxDxH): 6.2 x 2.3 x 1.6 in (158 x 58 x 41 mm)
Power consumption: 8mA @ 5VDC, 66mA @ 12VDC
Powered by E-2D/5D/16D
Operating temperature: 32 to 158°F (0 to 70°C)
Regulatory approvals: CE, RoHS
Compatible with E-FSC fiber converter/extender
Extends monitor connection up to 1.2 miles (2 km) from ENVIROMUX device